Fire doors, fire dampers and structural fire protection

You will understand the passive fire protection that holds a fire inside its space, and know how to test fire doors and dampers and spot the damage that refits and repairs leave behind.

Passive fire protection does nothing visible for the whole life of a ship. Steel bulkheads with insulation, self-closing fire doors, fire dampers in ventilation ducts and sealed cable penetrations simply sit there. In a fire they decide whether the fire stays in one cabin or one engine room, or spreads through the ship. They are also the first things to be damaged without anyone noticing: a door wedged open for a breeze, a damper seized with rust, a new cable run pushed through a bulkhead and sealed with builder’s foam.

Port State control inspectors know this. In the 2023 Paris MoU annual report, fire doors (3.2% of deficiencies) were singled out as one of the specific items with a high rate of non-compliance. This lesson shows how the passive system is built and how to keep it intact.

Sign up once to open this lesson and every other one in the Academy.

The first 2 lessons of each course are open to all. The rest need a free sign-up, which takes half a minute. We don't issue certificates, and we don't share your details.

Already signed up? Sign in

We use your details to run the Academy and to understand who reads it. If you tick the box, we'll also email you about new courses. You can ask us to delete your details at any time.

In this lesson

  • A port State control inspection of the passive fire protection
  • In plain words
  • In detail
  • What the rules say
  • Flag and class notes
  • Key numbers
  • What inspectors find
  • Quiz: 6 questions

A port State control inspection of the passive fire protection

A ship is divided into boxes that are meant to hold a fire for a set time. The walls and decks are fire-resisting divisions:

  • “A” class divisions are steel, stiffened and insulated. They stop smoke and flame for a one-hour standard fire test. The number after the A (A-60, A-30, A-15, A-0) is how many minutes the cold side stays below a set temperature rise. An A-60 bulkhead keeps the far side cool enough for 60 minutes; an A-0 bulkhead is bare steel that stops flames but lets heat through.
  • “B” class divisions are lighter, non-combustible panels, often in cabins and corridors. They stop flame for the first half hour.

Every hole in these boxes is a weak point. Doors must be as fire-resistant as the wall they are in, and many must close by themselves. Ventilation ducts must have fire dampers: steel flaps that snap shut when there is a fire, so the duct does not become a chimney. Pipes and cables must pass through tested penetration systems, not just a hole with filler.

The crew’s job is simple to say: doors must close, dampers must move, and nobody may make new holes without fixing them properly.

The divisions and how they are rated

SOLAS II-2/3 defines the classes. An “A” class division is steel or equivalent, suitably stiffened, insulated with approved non-combustible materials so that the average temperature on the unexposed side rises no more than 140°C, and no single point more than 180°C, within 60, 30, 15 or 0 minutes for A-60, A-30, A-15 and A-0, and it must stop smoke and flame to the end of the one-hour standard fire test. A “B” class division is non-combustible, with an average rise of no more than 140°C and 225°C at any point for 15 minutes (B-15) or 0 minutes (B-0), and stops flame to the end of the first half hour. Prototypes are tested to the Fire Test Procedures (FTP) Code, 2010, Part 3, which also covers fire dampers, windows, pipe penetrations and cable transits (Appendix 2). Fire door control systems are tested under Part 4.

The required rating between two spaces comes from the SOLAS II-2/9 tables (9.1 to 9.8), which depend on ship type and on the two spaces’ fire risk categories. Passenger ships are divided into main vertical zones by A class bulkheads; cargo ships use one of the protection methods IC, IIC or IIIC for accommodation. The approved fire plan and structural fire protection plan show the result for your ship.

Penetrations and insulation

  • Penetrations of A class divisions must be tested to the FTP Code, except steel pipes of at least 3 mm wall and 900 mm length without openings, insulated like the division.
  • Insulation is carried past penetrations, intersections and ends for at least 450 mm.
  • Uninsulated metal pipes through A-0 or B-0 divisions must melt above 950°C (A-0) or 850°C (B-0).
  • Repairs and alterations must keep at least the previous standard (SOLAS II-2/1.3).

Fire doors

Passenger ships: doors in main vertical zone bulkheads, galley boundaries and stairway enclosures (other than power-operated watertight doors and normally locked doors) must:

  • close themselves against an inclination of up to 3.5°;
  • close in about 10 to 40 seconds (hinged) or at 0.1 to 0.2 m/s (sliding) with the ship upright;
  • be released remotely from the continuously manned central control station, in groups or all together, and individually from both sides;
  • have no hold-back hooks that the central station cannot release;
  • re-close automatically after being opened locally, and close automatically if the control system or power fails;
  • have local power accumulators for at least ten full openings and closings after power failure;
  • show at the fire door panel whether each door is closed;
  • (sliding and power-operated) sound an alarm 5 to 10 seconds before moving and until closed.

Cargo ships: door fire resistance must equal the division’s; A class doors and frames of steel; B class doors non-combustible; doors in boundaries of category A machinery spaces reasonably gastight and self-closing; self-closing doors without hold-back hooks, though fail-safe remotely released hold-backs may be used. In corridor bulkheads, ventilation openings up to 0.05 m² are allowed in the lower half of cabin doors.

Fire dampers and ducts

For ships built on or after 1 January 2016 (resolution MSC.365(93)):

  • Automatic fire dampers are required in ducts with a free cross-section over 0.075 m² passing through A class divisions, fitted close to the division, closing automatically but also manually from both sides, with a visible position indicator.
  • All fire dampers must be manually operable from both sides; automatic dampers must have a fail-safe mechanism that closes them on loss of electric, hydraulic or pneumatic power; remotely operated dampers must be re-openable manually at the damper.
  • Dampers must be easily accessible. Dampers behind ceilings or linings need an inspection hatch marked with the damper’s identification number, and that number must also be on any remote control.
  • Ducts need inspection and cleaning hatches near the dampers, and the main inlets and outlets must be closable from outside the space, with marked operating positions.
  • Ducts of 0.02 m² to 0.075 m² through A class divisions get steel sleeves at least 3 mm thick and 900 mm long, insulated to the division’s rating.

Inspection and testing (MSC.1/Circ.1432)

Interval Fire doors Fire dampers and ventilation
Weekly Fire door control panel indicators lamp-tested
Quarterly All doors in main vertical zone bulkheads tested for local operation All fire dampers tested for local operation
Annually All remotely controlled doors tested for proper release All dampers tested for remote operation; galley ducts and filters free of grease; ventilation controls interlocked with fire systems tested

During rounds, also look at: door closers and seals, latches that engage by themselves, doors not wedged or tied back, damper indicators readable and in the open position in normal service, damper hatches marked and openable, penetrations not disturbed, insulation intact in machinery and stairway casings, and no new openings in the boundaries of CO2-protected spaces.

  • SOLAS regulation II-2/3.2 defines “A” class divisions as steel divisions insulated so the unexposed side rises no more than 140°C on average and 180°C at any point within 60, 30, 15 or 0 minutes, and preventing smoke and flame to the end of the one-hour standard fire test.1
  • SOLAS regulation II-2/9.3.1 requires penetrations of “A” class divisions to be tested in accordance with the FTP Code, except steel pipes of at least 3 mm wall thickness and 900 mm length without openings.1
  • SOLAS regulation II-2/9.3.4 requires insulation to be carried past penetrations, intersections and terminal points for at least 450 mm in steel and aluminium structures.1
  • SOLAS regulation II-2/9.4.1.1.4 requires fire doors in main vertical zone bulkheads, galley boundaries and stairway enclosures of passenger ships to be self-closing, to close in about 10 to 40 seconds (hinged), to be remotely released from the continuously manned central control station, and to close automatically if the control system or power fails.1
  • SOLAS regulation II-2/9.4.2 requires doors in cargo ships to have the same fire resistance as the division, doors in boundaries of category A machinery spaces to be reasonably gastight and self-closing, and self-closing doors to have no hold-back hooks other than fail-safe remotely released arrangements.1
  • SOLAS regulation II-2/9.7.3.1.3, for ships built on or after 1 January 2016, requires automatic fire dampers in ducts over 0.075 m² passing through “A” class divisions, closable manually from both sides and with a visible position indicator.3
  • SOLAS regulation II-2/9.7.3.3 requires all fire dampers to be manually operable from both sides, automatic dampers to fail safe on loss of power or pressure, and remotely operated dampers to be re-openable at the damper.3
  • SOLAS regulation II-2/9.7.1.3 requires fire dampers to be easily accessible, with marked inspection hatches where hidden behind ceilings and the damper identification number also on any remote control.3
  • SOLAS regulation II-2/14.2.1.1 requires structural fire protection, including fire-resisting divisions and the protection of openings and penetrations, to be “kept in good order”.1
  • MSC.1/Circ.1432, paragraphs 6.3, 6.4, 7.6 and 7.7, call for quarterly local tests of all fire dampers and main vertical zone doors, and annual tests of remote damper operation and remote door release.2
  • The 2010 FTP Code (resolution MSC.307(88), effective 1 July 2012), annex 1, Part 3 and Part 4, sets the tests for A, B and F class divisions, including fire dampers and penetrations, and for fire door control systems.4
  • Marshall Islands (Marine Notice 2-011-14, Rev. Aug/2025) lists fire doors (weekly panel, quarterly local, annual remote) and ventilation systems and fire dampers (quarterly local, annual remote) in its inspection table, and adds the ro-ro ventilation inspection guidelines of MSC.1/Circ.1515 for ro-ro ships.5
  • Bahamas (Marine Notice 79, version 2.2) lists fire doors and ventilation systems and fire dampers among the systems to be maintained under MSC.1/Circ.1432, as amended.6
  • Survey practice: under the HSSC survey guidelines, surveyors examine the structural fire protection, test the operation of fire doors and the fire dampers of ventilation ducts, and test the remote means of closing ventilation openings and stopping fans.7
  • Alterations: any change that affects fire-resisting divisions (new cable runs, refitted cabins, new doors) should be approved by the RO before work, using type-approved products, because SOLAS II-2/1.3 requires the ship to keep at least the standard it had.1
What Value
“A” class insulation limits Average rise 140°C, single point 180°C1
“A” class smoke and flame integrity To the end of the 1-hour standard fire test1
“B” class limits Average rise 140°C, single point 225°C; flame integrity 30 min1
Insulation past penetrations At least 450 mm1
Untested steel pipe penetration Wall at least 3 mm, length at least 900 mm1
Hinged fire door closing time (passenger ships) About 10 to 40 s1
Sliding fire door closing speed 0.1 to 0.2 m/s1
Fire door closing against inclination Up to 3.5°1
Door operations from local accumulators At least 101
Pre-movement alarm for remote sliding doors 5 to 10 s1
Duct area needing automatic fire damper (A class) Over 0.075 m²3
Fire damper local test Quarterly2
Fire damper remote test Annually2
  • Self-closing fire doors held open with wedges, ropes or hooks, closers removed or broken, and latches that do not engage. In the 2023 Paris MoU annual report, fire doors were one of the specific items with high non-compliance.8
  • Fire dampers seized, with missing or unreadable indicators, or not marked with identification numbers matching the fire plan; on Edinburgh Castle in 1998, none of the galley damper codes could be related to the ship’s drawings.9
  • Penetrations in A class bulkheads opened for new cables or pipes and closed with non-approved materials, and insulation removed and not replaced after repairs.1
  • In the 2012 Paris and Tokyo MOU fire safety campaign, fire protection systems and appliances were not maintained ready for use in 11% of Tokyo MOU inspections, the campaign’s worst result; passive protection was part of that question.10
May a cabin door be held open on a cargo ship?

Only if it is not one of the doors required to be self-closing. Your structural fire protection plan shows which doors those are; on cargo ships they include doors in the boundaries of category A machinery spaces. A self-closing door may only be held open by a hold-back device with a fail-safe remote release (SOLAS II-2/9.4.2.2).

Who may repair a fire door or replace a damper?

The crew can adjust closers and free dampers following the maker’s instructions. Replacing a door, damper or penetration with a different product, or altering a division, needs a type-approved product and the RO’s agreement, because the fire rating comes from the tested assembly.

Why must the damper indicator show "open" in normal service?

A damper must be open to let the ventilation work, and closed only in a fire or a test. The indicator lets the crew see at a glance that a damper has not closed by itself (for example after a fusible link failed) and that a closed one has really closed in an emergency.

What is the difference between a fire damper and a smoke damper?

SOLAS II-2/3, as amended by MSC.365(93), defines a fire damper as one that restricts the passage of fire and helps keep the division’s fire integrity; a smoke damper restricts smoke and hot gases but is not expected to contribute to the integrity of the division.

1What does the “60” in A-60 tell you?
2Which hold-back arrangement is allowed on a self-closing fire door on a cargo ship?
3How often should every fire damper be tested for local operation?
4A hinged fire door in a passenger ship’s stairway enclosure takes 55 seconds to close after release. What is the finding?
5What must an automatic fire damper do if its electric actuator loses power?
6Electricians propose to pass a new cable bundle through an A-60 bulkhead. What is required?
  1. 1

    IMO Resolution MSC.99(73), revised SOLAS chapter II-2 (adopted 5 December 2000, in force 1 July 2002), regulations II-2/1.3, 3.2, 3.4, 9.3, 9.4 and 14.2.1, as amended. https://wwwcdn.imo.org/localresources/en/KnowledgeCentre/IndexofIMOResolutions/MSCResolutions/MSC.99(73).pdf

  2. 2

    IMO MSC.1/Circ.1432, Revised guidelines for the maintenance and inspection of fire protection systems and appliances (31 May 2012), as amended by MSC.1/Circ.1516, annex, paragraphs 2, 4.3, 6.3, 6.4, 7.6 and 7.7 (consolidated copy annexed to Cayman Islands Shipping Notice 01/2014 Rev 2). https://www.cishipping.com/system/files/notices/documents/CISN%202014_01%20Rev%202%20with%20Annex.pdf

  3. 3

    IMO Resolution MSC.365(93), Amendments to SOLAS 1974 (adopted 22 May 2014, in force 1 January 2016), annex, regulation II-2/3 (new definitions 54 to 56) and II-2/9.7 (paragraphs 7.1 and 7.3). https://wwwcdn.imo.org/localresources/en/KnowledgeCentre/IndexofIMOResolutions/MSCResolutions/MSC.365(93).pdf

  4. 4

    IMO Resolution MSC.307(88), International Code for Application of Fire Test Procedures, 2010 (2010 FTP Code) (adopted 3 December 2010, effective 1 July 2012), annex 1, Parts 3 and 4. https://wwwcdn.imo.org/localresources/en/KnowledgeCentre/IndexofIMOResolutions/MSCResolutions/MSC.307(88).pdf

  5. 5

    Republic of the Marshall Islands Maritime Administrator, Marine Notice 2-011-14 (Rev. Aug/2025), Appendix A. https://www.register-iri.com/wp-content/uploads/MN-2-011-14.pdf

  6. 6

    Bahamas Maritime Authority, Marine Notice 79, Firefighting Equipment, version 2.2 (20 November 2025), paragraph 4.6. https://www.classnk.or.jp/hp/pdf/activities/statutory/solas/solas_treaty/fire_protection/circular/ci_fi_bahama.pdf

  7. 7

    IMO Resolution A.1186(33), Survey guidelines under the Harmonized System of Survey and Certification (HSSC), 2023, annex, (CA) 2.2.2.28 (cargo ship safety construction annual survey), (PR) 5.2.2.79 (passenger ship renewal survey) and (EA) 1.2.2.7. https://wwwcdn.imo.org/localresources/en/KnowledgeCentre/IndexofIMOResolutions/AssemblyDocuments/A.1186(33).pdf

  8. 8

    Paris MoU, Annual Report 2023, as summarised by the International Institute of Marine Surveying (IIMS). https://www.iims.org.uk/paris-mou-annual-report-2023/

  9. 9

    UK Marine Accident Investigation Branch, Report of investigation into fire in main galley of Edinburgh Castle on 21 August 1998, sections 1.7 and 2.5. https://assets.publishing.service.gov.uk/media/547c71a5ed915d4c0d000143/edinburgh_castle_fire.pdf

  10. 10

    Tokyo MOU, Report of the 2012 Concentrated Inspection Campaign (CIC) on Fire Safety Systems (November 2013), section 3, question 5a. https://www.tokyo-mou.org/wp/wp-content/uploads/Final-Tokyo-MOU-Report-FSS-CIC-public-web-site.pdf

Rules checked 20 October 2026. VSL Safety is not an approved training provider and doesn't issue certificates. These lessons don't replace STCW training, or the manufacturer's training and certification that service technicians need.