On 6 June 2022 a second officer on the tanker Seacross, alongside in Greece, was killed by a fire extinguisher. He was helping to dispose of condemned 9 litre cartridge-operated foam units. When one cap would not unscrew, he pressed the lever to empty it. The corroded base split at its weld seam and the body struck him in the chest. The extinguisher was 17 years old. The Bahamas Maritime Authority found that it and seven other badly corroded units had been passed at their annual service by a shore contractor only two weeks before the ship’s own officers condemned them.9 The same report records a 2021 fatality on an offshore unit with a corroded, condemned dry powder extinguisher.9 The UK MCA warns that fatalities “have previously occurred” when corroded extinguisher bases failed in use.8
An extinguisher is a pressure vessel that sits for years in salt air and vibration, then has to work at once. Servicing confirms that it will discharge, and that it will not fail as a pressure vessel. This lesson follows the cycle of resolution A.951(23) and what flags add to it.
Free sign-up
Sign up once to open this lesson and every other one in the Academy.
The first 2 lessons of each course are open to all. The rest need a free sign-up, which takes half a minute. We don't issue certificates, and we don't share your details.
In this lesson
- Annual extinguisher round: accommodation and engine room
- In plain words
- In detail
- What the rules say
- Flag and class notes
- Key numbers
- What inspectors find
- Quiz: 6 questions
Try it
Annual extinguisher round: accommodation and engine room
In plain words
Every extinguisher on board goes through a fixed cycle.
- Between services someone on board checks regularly that it is in place and has not been used. Most planned maintenance systems set this monthly; follow your flag notice and the maker’s instructions.
- Every year a competent person services it. Has it been used? Is the pressure right? Is the outside sound? Does it weigh what it should? Are the hose and nozzle clear, and can you read the instructions?
- Every five years one extinguisher of each type and year of manufacture is fired off at a fire drill, opened up and inspected inside.
- Every ten years each one goes to a test station. The body, and the gas cartridge if it has one, are filled with water and pressure-tested to prove they will not burst.
Any unit that is corroded, dented or damaged is taken out of service, even if the paperwork says it is in date. Condemned extinguishers are still pressure vessels. Leave the emptying and disposal to a specialist.
In detail
The annual inspection
A.951(23) paragraph 9.1 requires periodical inspection to the manufacturer’s instructions and service at intervals not exceeding one year. Paragraph 9.1.3 says service and inspection should only be done by, or under the supervision of, a person with demonstrable competence, using the inspection guide in table 9.1.3.1 The annual part of that guide:
| Item | What to check |
|---|---|
| Safety clip and indicators | Has the extinguisher been operated? |
| Pressure indicator | Where fitted, pressure within limits. Dust covers on gauges and relief valves in place. |
| External examination | Corrosion, dents or damage that may affect safe operation |
| Weight | Weigh it and compare with the fully charged mass |
| Hose and nozzle | Clear and undamaged |
| Operating instructions | In place and legible |
The UK MCA adds that plastic collars and similar covers that may hide the condition of the cylinder must be removed for the inspection.8
Inspection at recharge, and the five- and ten-year work
When an extinguisher is recharged, table 9.1.3 calls for three checks. Water and foam charges that are to be reused are checked for suitability. Powder must be free-flowing, with no caking, lumps or foreign bodies. Gas cartridges are examined for damage and corrosion.1
At five-yearly intervals, at least one extinguisher of each type manufactured in the same year is test-discharged as part of a fire drill (paragraph 9.1.1).1 After the test discharge, and at the five- and ten-year inspections, the guide requires these checks1:
- air passages, vent holes, hose, nozzle strainer, discharge tube and breather valve, operating and discharge controls, cleaned and lubricated as required;
- safety pin removable and lever undamaged;
- gas cartridge weighed and within prescribed limits;
- O-rings checked, and hose diaphragms replaced if fitted;
- interior of water, foam and powder bodies inspected for corrosion and lining deterioration;
- after recharge: reassembled to the maker’s instructions, maintenance label filled in with the full weight, mounting bracket checked, and a report completed.
At intervals not exceeding ten years, all extinguishers and their propellant cartridges are hydraulically tested to the recognised standard or the manufacturer’s instructions (paragraph 9.1.2).1 The test pressure is one of the markings A.951(23) paragraph 8.1 requires on every extinguisher. At manufacture, bodies with a service pressure up to 2.5 MPa are tested to 5.5 MPa or 2.7 times the normal working pressure, whichever is higher (paragraph 4.2).1
How UK practice labels the same work
The UK MCA’s MGN 276 maps A.951(23) onto the service levels of BS 5306-38:
| Type | Basic service | Extended service (test discharge) | Overhaul (hydraulic test) |
|---|---|---|---|
| Water, foam and water-based | Every year | Every 5 years | Every 10 years |
| Powder | Every year | Every 5 years | Every 10 years |
| Powder, primary sealed | Every year | Every 10 years | Every 10 years |
| CO2 | Every year | Every 5 years (only for cylinders previously hydraulically tested) | Every 10 years |
| Powder or foam, composite cylinder | Every year | Every 10 years | Every 10 years |
Primary sealed units go back to the manufacturer or supplier for recharge.8
Wheeled (mobile) extinguishers
Large wheeled units come under MSC.1/Circ.1432 rather than A.951(23)4:
- Monthly: in place, properly arranged and in proper condition (5.9).
- Annually: inspected to the maker’s instructions, accessible parts examined, cylinder hydrostatic test date checked, and powder units inverted to agitate the powder (7.12).
- Every 5 years: at least one of each type and year of manufacture visually examined (9.6).
- Every 10 years: all units and propellant cartridges hydrostatically tested by specially trained persons (10.5).
Spare charges
SOLAS regulation II-2/10.3.3.1 requires spare charges for 100% of the first ten extinguishers and 50% of the remaining extinguishers that can be recharged on board, with not more than sixty spare charges in total. Recharging instructions must be carried on board. For extinguishers that cannot be recharged on board, the ship carries extra extinguishers of the same type, capacity and number instead (10.3.3.2).2 Count each type separately, and round fractions up to the next whole number, as Liberia and the Marshall Islands state.56
Worked example. 25 rechargeable 6 kg powder extinguishers: 10 + 50% of 15 = 10 + 7.5, rounded up to 18 spare charges. With 140 extinguishers of one type the formula gives 10 + 65 = 75, so the cap applies and 60 spare charges are enough.
Only refills approved for that extinguisher may be used (FSS Code chapter 4, paragraph 3.1.2).3 A discharged extinguisher is recharged or replaced at once (SOLAS regulation II-2/14.2.1.2), and Liberia and the Marshall Islands add that partially emptied extinguishers should also be recharged.256
Condemning and disposing of extinguishers
Reject any extinguisher with corrosion, dents or damage that may affect safe operation, which is the external examination item of table 9.1.3.1 The Seacross investigation added lessons for the ship9:
- Mount extinguishers on brackets off the deck, so moisture is not trapped under the base. Give units exposed to the weather extra protection.
- Have condemned extinguishers emptied and disposed of by a suitably qualified specialist, not by the crew.
- When you do discharge an extinguisher (for example at the five-yearly test discharge), follow the maker’s instructions and keep the body away from yours.
- Do not accept a service certificate at face value. Look at the extinguishers yourself after the contractor leaves.
Who may do the work
The IMO text asks for “demonstrable competence”. Flags define it:
- Liberia accepts crew servicing of powder, foam and water extinguishers if the ship has calibrated tools and the maker’s instructions, the crew hold advanced fire-fighting training and are competent in the tasks of table 9.1.3, and the class surveyor is satisfied. Hydraulic tests go to a facility certified by a government agency or classification society and by the manufacturer, and the same facility should recharge the cylinder afterwards.5
- Marshall Islands: hydrostatic testing facilities must be certified by a government agency or recognised organisation, and accepted by the ship’s recognised organisation or the manufacturer.6
- Cyprus (where the manufacturer gives no other recommendation): third-party inspection at intervals not exceeding two years, contents checked yearly with recharge when the loss exceeds 10%, and internal inspection with a hydrostatic test by a third party at intervals not exceeding ten years.7
- United Kingdom: basic and extended services may be done on board under the supervision of an officer with an STCW II/2 or III/2 unlimited certificate and advanced fire-fighting.8
Records
A.951(23) paragraph 9.2 requires records showing the date of inspection, the type of maintenance and whether a pressure test was done.1 The maintenance label on each extinguisher shows the last service and the full weight.18 Keep the service supplier’s report and the hydraulic test certificates with the ship’s records.
Work it out
What the rules say
- Resolution A.951(23) paragraph 9.1 says extinguishers should be inspected to the maker’s instructions and “serviced at intervals not exceeding one year”.1
- Resolution A.951(23) paragraph 9.1.1 says at least one extinguisher of each type and year of manufacture should be test-discharged at five-yearly intervals, as part of a fire drill.1
- Resolution A.951(23) paragraph 9.1.2 says all extinguishers, with their propellant cartridges, should be hydraulically tested at intervals not exceeding ten years.1
- Resolution A.951(23) paragraph 9.1.3 says service and inspection should be done only by, or under the supervision of, a person with demonstrable competence, using the inspection guide in table 9.1.3.1
- SOLAS regulation II-2/10.3.3.1 requires spare charges for 100% of the first ten and 50% of the remaining rechargeable extinguishers, up to sixty, and recharging instructions on board.2
- SOLAS regulation II-2/10.3.3.2 requires extra extinguishers instead of spare charges for extinguishers that cannot be recharged on board.2
- MSC.1/Circ.1432 paragraph 10.5 says all wheeled extinguishers and propellant cartridges should be hydrostatically tested at least once every ten years by specially trained persons.4
Flag and class notes
- Liberia: annual examination by an authorised service facility unless trained crew service the extinguishers and class accepts it. CO2 contents verified every two years, for example by weighing in front of the surveyor. Hydraulic test date permanently marked on the body.5
- Marshall Islands: annual service and the ten-yearly hydrostatic test are stated as “must”; the five-yearly test discharge “should” be done. The recognised organisation’s surveyor or a flag inspector may require a hydrostatic test whenever visual examination suggests a defect.6
- Cyprus: third-party inspection every two years, as above.7
- Class: the class surveyor carries out the annual Safety Equipment survey for most flags and must be satisfied with the condition of the extinguishers. Liberia allows the surveyor to accept a servicing certificate from a facility acceptable to the society.5 Ask your class society for its list of approved service suppliers in the next port.
Key numbers
| What | Value |
|---|---|
| Annual service | Not exceeding 1 year1 |
| Test discharge | 1 of each type and year of manufacture, every 5 years1 |
| Hydraulic test of body and cartridge | Not exceeding 10 years1 |
| Construction test pressure (service pressure up to 2.5 MPa) | 5.5 MPa or 2.7 × working pressure, whichever is higher1 |
| Spare charges | 100% of first 10 + 50% of the rest, maximum 602 |
| Cyprus: recharge when contents loss exceeds | 10%7 |
| Cyprus: third-party inspection | Not exceeding 2 years7 |
| Seacross extinguisher age at failure | 17 years9 |
What inspectors find
- Corroded extinguishers passed at service. On Seacross, eight of the units the shore contractor had just passed were condemned by the ship’s own officers within two weeks.9
- Fire-fighting equipment and appliances were the second-largest group of deficiencies in the Tokyo MOU 2023 fire safety campaign: 392 findings, 57 of them grounds for detention.10
- Discharged or partly discharged extinguishers left in place, against SOLAS regulation II-2/14.2.1.2 and flag notices.25
- Too few spare charges, often because the count was not split by type or the 50% was rounded down.25
- Hydraulic test dates past ten years, or no test date permanently marked on the body, which Liberia and the Marshall Islands require.56
FAQ
Can the crew do the five-yearly test discharge?
Yes. A.951(23) places it “as part of a fire drill”. The inspection after discharge (passages, O-rings, interior, recharge and label) must be done by a competent person, on board or by a service supplier, as your flag allows.
Does the ten-year interval start from the year of manufacture?
It starts from manufacture, and then from the last hydraulic test stamped on the body. Read the marking on the unit. The Seacross extinguisher was hydraulically tested at eight years, ahead of its ten-year date.
Our supplier says composite-bodied extinguishers do not need a five-year test discharge. Is that right?
UK guidance based on BS 5306 sets the extended service of composite powder and foam units at ten years. A.951(23) itself does not distinguish by body material. Follow your flag’s notice and the manufacturer’s instructions, and record what you did.
What should we do with a condemned extinguisher?
Mark it clearly, take it out of service and replace it at once. Store it safely and land it to a specialist who can depressurise and dispose of it. Do not try to empty it with the trigger or force the cap.
Quiz6 questions
Sources
- 1
IMO Resolution A.951(23), Improved guidelines for marine portable fire extinguishers, adopted 5 December 2003, annex paragraphs 4.2, 8.1, 9.1 to 9.4 and table 9.1.3. https://wwwcdn.imo.org/localresources/en/KnowledgeCentre/IndexofIMOResolutions/AssemblyDocuments/A.951(23).pdf
- 2
IMO Resolution MSC.99(73), revised SOLAS chapter II-2, adopted 5 December 2000, regulations II-2/10.3.2.3, 10.3.3 and 14.2.1.2. https://wwwcdn.imo.org/localresources/en/KnowledgeCentre/IndexofIMOResolutions/MSCResolutions/MSC.99(73).pdf
- 3
IMO Resolution MSC.98(73), International Code for Fire Safety Systems (FSS Code), chapter 4, paragraph 3.1.2. https://wwwcdn.imo.org/localresources/en/KnowledgeCentre/IndexofIMOResolutions/MSCResolutions/MSC.98(73).pdf
- 4
IMO MSC.1/Circ.1432, Revised guidelines for the maintenance and inspection of fire protection systems and appliances, 31 May 2012, paragraphs 5.9, 7.12, 9.6 and 10.5 (copy annexed to Cayman Islands Shipping Notice 01/2014 Rev 2). https://www.cishipping.com/system/files/notices/documents/CISN%202014_01%20Rev%202%20with%20Annex.pdf
- 5
Liberia Maritime Authority, Marine Notice FIR-001 Rev. 02/26, Fire-protection systems and appliances, sections 6.1 to 6.8 (6.4.4 on partially emptied extinguishers). https://www.liscr.com/sites/default/files/online_library/FIR-001.pdf
- 6
Republic of the Marshall Islands Maritime Administrator, Marine Notice 2-011-14 Rev. Aug/2025, section 8 (8.2, 8.4). https://www.register-iri.com/wp-content/uploads/MN-2-011-14.pdf
- 7
Cyprus Shipping Deputy Ministry, Circular No. 41/2021, paragraph 3.1 and section 6 (annexed to IRClass Technical Circular 008/2022). https://www.irclass.org/media/5913/technical-circular-no008.pdf
- 8
UK Maritime and Coastguard Agency, MGN 276 (M+F) Amendment 1, Fire protection: maintenance of portable fire extinguishers, 2023, paragraphs 1.1 and 1.4 to 1.8 and table 1. https://www.gov.uk/government/publications/mgn-276-mf-amendment-1-fire-protection-maintenance-of-portable-fire-extinguishers/mgn-276-mf-amendment-1-fire-protection-maintenance-of-portable-fire-extinguishers
- 9
Bahamas Maritime Authority, Report of the marine safety investigation into the failure of a condemned fire extinguisher during decommissioning resulting in the loss of a life on 06 June 2022 (M/T Seacross), issued 27 June 2023, sections 1 to 4. https://www.bahamasmaritime.com/wp-content/uploads/2023/06/BMA-MSI-Final-Report-Seacross-Fire-extinguisher-failure-fatality.pdf
- 10
Tokyo MOU, Report of the 2023 Concentrated Inspection Campaign (CIC) on Fire Safety, table 3. https://www.tokyo-mou.org/wp/wp-content/uploads/CIC-ON-FIRE-SAFETY-2023-Report-public.pdf
Rules checked 20 October 2026. VSL Safety is not an approved training provider and doesn't issue certificates. These lessons don't replace STCW training, or the manufacturer's training and certification that service technicians need.