A self-contained breathing apparatus (SCBA) is the one piece of fire-fighting equipment that keeps a person alive inside the fire. It also fails silently. A cylinder can read full and hold contaminated air. A face mask can look fine and leak at the seal. A demand valve can stick. A low-air warning can stay silent until the wearer is out of air, deep in a smoke-filled engine room. That is why the rules check the apparatus every week and test the air and the cylinders on fixed cycles.
This lesson goes through the apparatus part by part, then covers the checks, the air quality standard, cylinder testing and the spare charges the ship must carry.
Free sign-up
Sign up once to open this lesson and every other one in the Academy.
The first 2 lessons of each course are open to all. The rest need a free sign-up, which takes half a minute. We don't issue certificates, and we don't share your details.
In this lesson
- Parts of a fire-fighter's SCBA
- In plain words
- In detail
- What the rules say
- Flag and class notes
- Key numbers
- What inspectors find
- Quiz: 6 questions
Try it
Parts of a fire-fighter's SCBA
In plain words
The SCBA in a fire-fighter’s outfit is a cylinder of clean, dry compressed air on a back frame. A reducer brings the pressure down, and a demand valve on the face mask gives the wearer air as they breathe in. A gauge shows how much is left, and a whistle or other alarm warns before the air runs low.
Four things have to be right:
- Enough air. At least 1,200 litres, or 30 minutes for other types of apparatus.
- A warning before the air runs out. It must sound before only 200 litres are left.
- Clean air. If the ship fills its own cylinders, the compressor’s air is tested against a breathing air standard.
- Sound cylinders. They are pressure-tested on a fixed cycle, and spare full cylinders are kept on board.
The crew check the gauges every week and the full outfit every month. Each year the masks, demand valves and any compressor air are checked. Every five years the steel cylinders go ashore for hydrostatic testing.
In detail
What the FSS Code requires
FSS Code chapter 3, paragraph 2.1.2, as replaced by resolution MSC.339(91)12:
- 2.1.2.1: a self-contained compressed air breathing apparatus with at least 1,200 l of air in its cylinders, or another self-contained apparatus able to work for at least 30 minutes. All air cylinders must be interchangeable.
- 2.1.2.2: an audible alarm and a visual or other device that alerts the user before the air in the cylinder is reduced to no less than 200 l.
MSC.1/Circ.1499 interprets the visual device: a pressure gauge that lets the user read that the air has dropped to no less than 200 l may count, “regardless of the need for supplemental lighting”.6
SOLAS regulation II-2/10.10.1.2, added by resolution MSC.338(91), makes SCBA in fire-fighter’s outfits meet paragraph 2.1.2.2 by 1 July 2019. Regulation II-2/1.2.5 applies this to ships built before 1 July 2012 as well, so every ship is now covered.4
Rule of thumb on capacity: free air is roughly the cylinder’s water capacity multiplied by its filling pressure. By this estimate a 6 l cylinder at 200 bar holds 1,200 l. At these pressures real air is less compressible than the estimate assumes, so the true content is a few per cent lower at 200 bar and noticeably lower at 300 bar. Use the maker’s figure for the rated air volume.
Spare charges and recharging
SOLAS regulation II-2/10.10.2.5 requires two spare charges for each required breathing apparatus. Cargo ships, and passenger ships carrying not more than 36 passengers, need only one spare charge per apparatus if they have a suitably located means of fully recharging the cylinders free from contamination.3 Passenger ships carrying more than 36 passengers built on or after 1 July 2010 must have a recharging means (regulation 10.10.2.6, added by MSC.269(85)). That is either a breathing air compressor of at least 60 l/min per required apparatus, up to 420 l/min in total, or a high-pressure storage system of at least 1,200 l per required apparatus, up to 50,000 l of free air.13
Drills use air too. SOLAS regulation II-2/15.2.2.6 requires either an on-board means of recharging the cylinders used in drills, or “a suitable number of spare cylinders”.4 MSC.1/Circ.1555 interprets this as at least one set of cylinders for each mandatory breathing apparatus, unless the safety management system requires more. A set is the number of cylinders needed to operate one apparatus. No extra drill cylinders are needed for apparatus required by regulation II-2/19 or the IMSBC, IBC or IGC Codes.7
The inspection cycle
MSC.1/Circ.1432 sets the minimum5:
| When | Check | Paragraph |
|---|---|---|
| Weekly | All breathing apparatus and EEBD cylinder gauges in the correct pressure range | 4.5 |
| Monthly | Lockers for fire-fighting equipment hold their full inventory, in serviceable condition | 5.5 |
| Annually | Air quality of any on-board recharging system; face masks and air demand valves serviceable | 7.8.1, 7.8.2 |
| Every 5 years | Hydrostatic test of all steel SCBA cylinders. Aluminium and composite cylinders tested to the satisfaction of the Administration. | 9.4 |
Also follow the manufacturer’s maintenance instructions (paragraph 3.4).5 A practical weekly or monthly round, using the maker’s checklist, normally covers:
- the cylinder pressure on the gauge;
- the cylinder valve opening and a high-pressure leak check: close the valve and watch the gauge fall;
- the whistle sounding as the pressure is vented;
- the mask seal and the demand valve working;
- straps, harness and lifeline intact;
- the test date on each cylinder, including the spares.
Ships carrying chemicals or gas in bulk have stricter rules. Cyprus quotes paragraph 14.2.6 of the IBC Code: monthly inspection by a responsible officer, recorded in the log-book, and an annual inspection and test by an expert. Liberia applies the same monthly and annual checks to ships under the IGC and IBC Codes.910
Breathing air quality
MSC.1/Circ.1432 paragraph 7.8.1 asks for an annual check of air quality from any on-board recharging system.5 Liberia specifies BS EN 12021, Compressed gases for breathing apparatus, or an equivalent standard acceptable to the class surveyor.9 Published summaries of EN 12021:2014 give these main limits11:
| Component | Limit (EN 12021:2014) |
|---|---|
| Oxygen | 21 ± 1% |
| Carbon monoxide | ≤ 5 ppm |
| Carbon dioxide | ≤ 500 ppm |
| Oil | ≤ 0.5 mg/m³ |
| Water | Limit depends on the cylinder’s filling pressure; see the standard |
| Odour and taste | None significant |
Water matters on deck: moisture in high-pressure cylinders causes internal corrosion and can freeze demand valves in cold weather. Keep the compressor filters to the maker’s change intervals, site the compressor intake away from engine and boiler exhausts, and keep the air test certificate with the BA records.
Cylinder testing
- Steel: hydrostatic test every five years (MSC.1/Circ.1432 paragraph 9.4).5 Liberia and the Marshall Islands require the test date to be permanently marked on the cylinder.89
- Aluminium and composite: “to the satisfaction of the Administration”.5 Flags usually follow the cylinder maker and the class society. Composite cylinders often carry a limited service life marked on the label, after which they are scrapped whatever their test results. Check the label at each inspection.
- New ships: Liberia and the Marshall Islands let the first five-year test be harmonised with the first special survey dry-docking if the cylinder’s first date stamp is not more than six months before delivery.89
- Cyprus requires internal inspection and hydrostatic testing of SCBA bottles, including spares and the pressure vessels of the charging system, by a third party at intervals not exceeding five years. It also requires a third-party inspection of the apparatus every two years.10
What the rules say
- FSS Code chapter 3, paragraph 2.1.2.1, requires at least 1,200 l of air (or 30 minutes for other types), and all breathing apparatus air cylinders to be interchangeable.2
- FSS Code chapter 3, paragraph 2.1.2.2, requires “an audible alarm and a visual or other device” that warns the user before the air is reduced to no less than 200 l.2
- SOLAS regulation II-2/10.10.1.2 requires the SCBA of fire-fighter’s outfits to comply with paragraph 2.1.2.2 by 1 July 2019, on all ships.4
- SOLAS regulation II-2/10.10.2.5 requires two spare charges for each required breathing apparatus, or one where cargo ships and passenger ships with no more than 36 passengers can fully recharge the cylinders free from contamination.3
- SOLAS regulation II-2/15.2.2.6 requires an on-board means of recharging the cylinders used in drills, or a suitable number of spare cylinders.4
- MSC.1/Circ.1555 interprets that number as at least one set of cylinders for each mandatory breathing apparatus, unless the SMS requires more.7
- MSC.1/Circ.1432 paragraphs 4.5, 7.8 and 9.4 call for a weekly gauge check, annual checks of air quality, face masks and demand valves, and a five-yearly hydrostatic test of steel SCBA cylinders.5
Flag and class notes
- Liberia: weekly check for leaks; examination at every annual Safety Equipment survey; air quality to BS EN 12021 or an equivalent accepted by the class surveyor; hydrostatic test every five years, with the interval for ultra-lightweight cylinders set by the manufacturer and class.9
- Marshall Islands: weekly check of the pressure range; monthly inspection by a ship’s officer; annual inspection and test by competent crew unless the manufacturer requires an authorised agent; five-yearly hydrostatic test.8
- Cyprus: third-party inspection at intervals not exceeding two years; masks, hoses, regulators and air quantity and quality checked every year, and by a third party every two years; recharge when the loss exceeds 10%; 200% spare charged bottles unless there is a means of recharging.10
- Class: the annual survey includes the SCBA and any compressor. Some manufacturers require an annual service by their authorised agent, and the Marshall Islands notice recognises this.8 Check the maker’s manual and your class society’s list of approved service suppliers.
Key numbers
| What | Value |
|---|---|
| Minimum air volume | 1,200 l (or 30 min for other types)2 |
| Low-air warning before air falls to | No less than 200 l2 |
| Low-air warning required on all ships | Since 1 July 20194 |
| Lifeline | At least 30 m, 3.5 kN static load for 5 min1 |
| Spare charges per required apparatus | 2 (1 with on-board recharging)3 |
| Drill spares | At least 1 set of cylinders per mandatory apparatus7 |
| Steel cylinder hydrostatic test | Every 5 years5 |
| Passenger ship compressor (over 36 passengers, built from 1 July 2010) | At least 60 l/min per apparatus, up to 420 l/min13 |
| Carbon monoxide limit, EN 12021:2014 | ≤ 5 ppm11 |
What inspectors find
- No low-air warning, or a warning that does not sound, on older apparatus. This is a breach of SOLAS regulation II-2/10.10.1.2 since 1 July 2019.4
- Cylinders past their hydrostatic test date, often the spares stored separately from the sets.59
- No air quality certificate for the ship’s own breathing air compressor, or an out-of-date one.59
- Spare cylinders used in drills and not refilled, so the ship no longer has the spares SOLAS regulation II-2/10.10.2.5 requires.34
- Fire-fighting equipment and appliances in general: 392 deficiencies in the Tokyo MOU 2023 fire safety campaign, 57 of them grounds for detention.12
FAQ
Can we use 300 bar cylinders on a 200 bar set?
Only if the maker approves that combination for that apparatus. FSS Code chapter 3 requires all cylinders on board to be interchangeable, so mixing types that do not fit every set is a deficiency.
Our ship has a breathing air compressor. Do we still need two spare charges per set?
On cargo ships and passenger ships with no more than 36 passengers, one spare charge per apparatus is enough if the compressor (or other means) can fully recharge the cylinders free from contamination. You still need spares for drills or the means to refill after drills.
Is the gauge enough as the visual warning?
Yes. MSC.1/Circ.1499 accepts a gauge that lets the wearer read that the remaining air has fallen to 200 l, even if light is needed to read it. The audible alarm is still required.
Who tests the cylinders?
A cylinder test station acceptable to your flag and class. The crew check the dates. Liberia and the Marshall Islands require the hydrostatic test date to be permanently marked on each cylinder.
Quiz6 questions
Sources
- 1
IMO Resolution MSC.98(73), International Code for Fire Safety Systems (FSS Code), adopted 5 December 2000, chapter 3, paragraphs 2.1 and 2.1.3. https://wwwcdn.imo.org/localresources/en/KnowledgeCentre/IndexofIMOResolutions/MSCResolutions/MSC.98(73).pdf
- 2
IMO Resolution MSC.339(91), Amendments to the FSS Code, adopted 30 November 2012, in force 1 July 2014, chapter 3, paragraphs 2.1.2.1 and 2.1.2.2. https://wwwcdn.imo.org/localresources/en/KnowledgeCentre/IndexofIMOResolutions/MSCResolutions/MSC.339(91).pdf
- 3
IMO Resolution MSC.99(73), revised SOLAS chapter II-2, adopted 5 December 2000, regulation II-2/10.10.2.5. https://wwwcdn.imo.org/localresources/en/KnowledgeCentre/IndexofIMOResolutions/MSCResolutions/MSC.99(73).pdf
- 4
IMO Resolution MSC.338(91), Amendments to SOLAS 1974, adopted 30 November 2012, in force 1 July 2014, regulations II-2/1.2.5, 10.10.1 and 15.2.2.6. https://wwwcdn.imo.org/localresources/en/KnowledgeCentre/IndexofIMOResolutions/MSCResolutions/MSC.338(91).pdf
- 5
IMO MSC.1/Circ.1432, Revised guidelines for the maintenance and inspection of fire protection systems and appliances, 31 May 2012, paragraphs 3.4, 4.5, 5.5, 7.8 and 9.4 (copy annexed to Cayman Islands Shipping Notice 01/2014 Rev 2). https://www.cishipping.com/system/files/notices/documents/CISN%202014_01%20Rev%202%20with%20Annex.pdf
- 6
IMO MSC.1/Circ.1499, Unified interpretation of chapter 3 of the FSS Code, 12 January 2015 (copy published by Traficom, Finland). https://www.traficom.fi/files/media/regulation/22550-MSC_1-Circ_1499_-_tulkinta_Chapter_3_Of_The_Fss_Code_%28Secretariat%29.pdf
- 7
IMO MSC.1/Circ.1555, Unified interpretations of SOLAS chapter II-2, 25 November 2016, interpretation of regulation II-2/15.2.2.6 (copy published by Traficom, Finland). https://www.traficom.fi/files/media/regulation/24353-MSC_1-Circ_1555_-_SOLAS_II-2_Fire_Satety_.pdf
- 8
Republic of the Marshall Islands Maritime Administrator, Marine Notice 2-011-14 Rev. Aug/2025, section 10. https://www.register-iri.com/wp-content/uploads/MN-2-011-14.pdf
- 9
Liberia Maritime Authority, Marine Notice FIR-001 Rev. 02/26, Fire-protection systems and appliances, section 7. https://www.liscr.com/sites/default/files/online_library/FIR-001.pdf
- 10
Cyprus Shipping Deputy Ministry, Circular No. 41/2021, section 7 (annexed to IRClass Technical Circular 008/2022). https://www.irclass.org/media/5913/technical-circular-no008.pdf
- 11
EN 12021:2014, Respiratory equipment: compressed gases for breathing apparatus (CEN standard, purchase from national standards bodies). Limits as given in published summaries of the standard; check the current edition.
- 12
Tokyo MOU, Report of the 2023 Concentrated Inspection Campaign (CIC) on Fire Safety, table 3. https://www.tokyo-mou.org/wp/wp-content/uploads/CIC-ON-FIRE-SAFETY-2023-Report-public.pdf
- 13
IMO Resolution MSC.269(85), Amendments to SOLAS 1974, adopted 4 December 2008, in force 1 July 2010, regulation II-2/10.10.2.6. https://wwwcdn.imo.org/localresources/en/KnowledgeCentre/IndexofIMOResolutions/MSCResolutions/MSC.269(85).pdf
Rules checked 20 October 2026. VSL Safety is not an approved training provider and doesn't issue certificates. These lessons don't replace STCW training, or the manufacturer's training and certification that service technicians need.